QUICK CHECKS
Fire doors & notices
- Match the door
- A self-closing door notice tells people not to obstruct it or keep it propped open. A door held open by an automatic device needs different wording. Confirm the fire/smoke door type and exact wording on the approved door schedule.
- Position & faces
- Fit on or adjacent to the applicable door, visible on the required approach. Horizontal exits, two-way smoke doors and final discharge doors require the specified notices on both faces. For applicable automatically held-open doors, use the adjacent wall or both door faces as required.
- Lettering & fixing
- Where NCC D3D28 applies, use contrasting capitals at least 20 mm high. Confirm exact wording and faces; use the approved door-assembly fixing detail and keep hardware and seals clear.
NSW fire-exit offence notices
- This separate NSW-only notice follows section 108 of the Environmental Planning and Assessment (Development Certification and Fire Safety) Regulation 2021. Fit prominently beside access doorways, outside the fire-isolated stairway, passageway or ramp. Do not substitute it for another state’s notice.
Sources & project checks
NCC notes retain the existing NCC 2022 references. Use the code edition, jurisdiction and approved sign schedule for your project.
Matching products
Quick checks support your approved project specification; they do not certify a sign or installation.